250A 3 Poles Moulded Case Circuit Breaker MCCB/ELCB

0 votes
asked Jul 2, 2022 in 3D Segmentation by netcec001 (677,950 points)
ELCB TRE SERIES

 

Standard

TRE series circuit breaker and auxiliaries comply with the following international standard:

1.IEC/EN 60947-1

Low-voltage switchgear and controlgear-part 1: General rules;

2.IEC/EN 60947-2

Low-voltage switchgear and controlgear-part 2: Circuit breakers;

 

TRE series ELCB(Standard use environment for TRE series ELCB)

1. Ambient temperature: Within the range of -5ºC--+40ºC(However, the average for the duration of 24 hours must not exceed 35ºC);

2. Altitude: 2000m or less

3. Installation class: III

4. The magnetic field near the instalation site should not be more than five times the earth magnetic field in any direction.

5. Pollution: II

 

Classification:

According to the poles:                                          3-poles, 4-poles

According to the breaking capacity:                         S-type, H-type

According to the rated current:                               Fix type, Adjustable type(08In-1.0In)

According to the trip action time:                            Fix type, Adjustable type(0.1s/0.3s/0.5s or 0.45s/1.0s/2.0s)

According to the rated residual current:                   Fix type, Adjustable(30mA/100mA/300mA/500mA)

 

 

Technical data table:

 

 

 

 

 

Ampere frame size

 

 

TREF4(250A)

 

 

 

 

Breaking capacity code

 

 

S

 

 

H

 

 

 

 

Product code and poles

 

 

3P

 

 

4P

 

 

3P

 

 

4P

 

 

 

 

TREF4-S3

 

 

TREF4-S4

 

 

TREF4-H3

 

 

TREF4-H4

 

 

 

 

Protective function

 

 

Over load & Short circuit & Ground fault

 

 

 

 

Rated current, In(A)

 

 

100, 125, 160, 180, 200, 225, 250

 

 

 

 

Rated residual current

 

 

Operating, IΔn(mA)

 

 

30, 50, 100, 200, 300, 500

 

 

 

 

Non-operating, IΔno(mA)

 

 

15, 25, 50, 100, 150, 250

 

 

 

 

Adjustable part

 

 

Rated current setting(0.8In-1.0In)

 

 



 

 



 

 



 

 



 

 

 

 

Lockup device for operating handle

 

 



 

 



 

 



 

 



 

 

 

 

Residual current, IΔn

 

 

30mA/100mA/300mA/500mA

 

 

 

 

Trip action time

 

 

0.1s/0.3s/0.5s

 

 

 

 

Rated operational voltage, Ue(V), AC 50/60 Hz

 

 

240/415

 

 

 

 

Rated insulation voltage, Ui(V)

 

 

1000

 

 

 

 

Rated impulse withstand voltage, Uimp(kV)

 

 

8

 

 

 

 

Residual current off-time at IΔn ,Sec (s)

 

 

0.1

 

 

 

 

Standard

 

 

Conformity with IEC/EN 60947-2

 

 

 

 

Rated frequency(Hz)

 

 

50/60

 

 

 

 

Rated short-circuit breaking capacity, Icu(kA)

 

 

 

 

AC

 

 

240V

 

 

50

 

 

65

 

 

 

 

415V

 

 

37

 

 

50

 

 

 

 

Ics=% * Icu

 

 

100%

 

 

 

 

Mechanical life(circle)

 

 

7000

 

 

 

 

Electrical life(circle)

 

 

1000

 

 

 

 

Dimension:

Length*Width*Height

 

 

2-poles

 

 

-

 

 

 

 

3-poles

 

 

165*105*60

 

 

 

 

4-poles

 

 

165*140*60

 

 

 

 

 

Built-in accessory:

 